I based this on your suggestion that the cooker is 32kw 133 amps dont think so quote i did at first think 6mm flex would not comply.
Cooker connection unit for 10mm cable.
Y 2020 m 9 d 21 h 15cst.
Oven and hob both have 6mm2 cables can they be terminated asked by.
Try to keep the cooker to the side of the control unit instead of directly in front of it.
When wiring an electric coo.
I would be wary of tiling over it as you are effectively losing the safe zone unless its right in the corner.
Find a clear spot for the control unit used to wire the cooker to the wall.
Free next day delivery available free collection in 5 minutes.
Cables so you should have no issues fitting 2 x 6mm sup2.
Maccatw74 hi maccatw74 yes the terminal capacity for this connection unit is up to 3 x 10mm sup2.
In which case if its a blank plate then i think i d just go for 60amp connectors i would think the 2 10mm cores would pass each other in the connector so doubling up the connection if you know what i mean.
I have purchased a rangemaster dual fuel cooker and i have a question regarding the wiring of it to the cooker connection unit.
You cant join 10mm cable using a 30 connection as 10mm is rated at 53 amps.
It prevents heat from the cooker blasting directly onto the wires.
This video shows how to wire an electric cooker to an electric cooker circuit via the cooker connection unit often called a ccu.
Slimline 45a cooker connection unit.
Either that or a crimp if the cable is long enough to get a crimper in the box.
No cooker switch in the kitchen just mcb and rcd in.
You are most likely going to place the new cooker where the old one is in your home.
You cant use 6mm to connect the cooker.